Océ 2600 & 3100 Power Connection
/NR/rdonlyres/emsy6wurls2sk5ma2rr4fuzspjyxbnaaj7uj66qggq45uehkzl2kvzddh7spl6xeg75rfgvrnwiwpu4mykqagmoimhg/c_red.gif

The requirements for the Océ 2600 and 3100 are:

3 phase + Neutral and Earth is desirable, but the machine can be connected to a suitable single phase supply.
The supply should be terminated in a BS EN 60309 (formerly BS4343) socket with interlocked isolator switch. The machine can be supplied with a 3 metre flexible cable complete with a matching plug.
HRC fuses are recommended for overload protection.
If a residual current protection device is also fitted, the minimum differential trip current should be not less than 30mA to prevent nuisance tripping.
The average power consumption is approximately 3.6kW. The maximum current for 3 phase connection is 16 amps per phase; for a single phase connection it is 30 amps.

SOCKET

3 phase: 16 amp 5 pin BS EN 60309 switched outlet (e.g. RS Components stock Nº 490-116)
Single Phase: 32 amp 3 pin BS EN 60309 switched outlet (e.g. RS 490-605)

PERMANENT CONNECTION (non-preferred)

If a socket as above cannot be provided, the machine can be connected to a fixed isolator switch, in which case the customer's qualified electrician must supply the flex and make the connection to the machine:

3 Phase + Neutral & Earth: 20 amp isolator. We recommend 2.5mm2 5 core flex to the machine.
Single Phase: 32 amp isolator. We recommend 4mm2 3 core flex to the machine.
 